In a motor feeder the breaker and contactor each own a job: one clears short circuits, the other switches the motor. Bad coordination burns the contactor or defeats protection.
The breaker clears short-circuit and severe over-load current through its magnetic trip in milliseconds. The contactor switches the motor frequently under command of the control circuit and carries no short-circuit protection. Wired in series, the breaker upstream protects the wiring, the contactor downstream runs the motor, and a thermal relay handles over-load. This keeps the contactor contacts away from short-circuit current so they last.
Size the contactor to the motor full-load current: a 7.5kW/15A motor takes an 18~25A contactor. Size the breaker for the circuit, typically setting its magnetic trip at 1.5~2.5 times rated current so the 5~7 times starting current does not trip it. A typical set is a 25A breaker with an 18~25A contactor and a 15A thermal setting. Keep the contactor AC-3 category and the breaker breaking capacity matched, with upstream selectivity.
Wrong coordination hurts both ways. A breaker set too small trips on start, so the fitter raises it until shorts no longer trip and the cable burns. A contactor sized small welds its contacts under chronic overload while the breaker stays put below short-circuit level. Conflicting thermal and breaker settings let the breaker trip first, robbing the thermal relay of its job. Keep the three stages each guarding its own band.
| Item | Breaker | Contactor |
|---|---|---|
| Duty | Short-circuit/line | Start-stop control |
| Setting basis | 1.5~2.5x Ie magnetic | Size to Ie |
| 15A motor example | 25A breaker | 18~25A contactor |
| Over-load | Backstop | Thermal relay does it |
| Start current | Must ride 5~7x | Frequent make-break |
| Wrong result | Trips or won`t trip | Welds if small |
Rule: short breaker, start-stop contactor, over-load thermal relay, three stages each guard a band. Size and set by motor current step by step, ride the starting current, keep upstream selectivity. On old retrofits check the three ratings one by one.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor feeder coordination per GB/T 5226.1; contactor and breaker coordination per GB/T 14048.4 and GB/T 14048.2. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.