Skin effect in AC and its impact on high-frequency wire choice

The higher the frequency, the more current flows near the surface and the centre carries almost nothing. This page gives the skin depth formula, its effect on wire sizing, and why stranded or tubular conductors are used at high frequency.

1. How it works

Alternating current induces eddies that push current to the surface, shrinking the effective area and raising the AC resistance. The penetration depth delta equals root of two rho over omega mu, with rho resistivity, mu permeability and omega two pi f. At 50 Hz copper delta is about 9.3 millimeter, at 1 kHz 2.1, at 10 kHz 0.66 and at 100 kHz 0.21 millimeter.

2. Practice and pitfalls

When the wire radius far exceeds delta the centre copper is wasted and AC resistance can be several times the DC value. The fix is stranded Litz wire so each fine strand stays shallower than delta, or tubular and flat conductors that add surface. At power frequency with diameter under twice delta, about 18 millimeter, skin effect is negligible and no special wire is needed.

3. Skin depth reference

FreqCu deltaChoice
50 Hz9.3 mm普通
1 kHz2.1 mmthick ok
10 kHz0.66 mmstranded
100 kHz0.21 mmLitz
1 MHz0.066 mmfine multi
Fixmore areastrand/tube

4. Notes

Think about skin once frequency reaches the kilohertz range; power wiring at 50 Hz mostly need not. For induction, drive output and RF use stranded or Litz wire, never a solid bar. Check delta at the working frequency and keep radius within twice delta for economy.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductors follow GB/T 3956 and terms IEC 60050. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Solid thick bar at high frequency spikes resistance and heats badly
② Sizing by DC resistance ignores AC resistance and over-temp
③ Busbars stacked too close shield each other and lose current

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.