The power factor controller is the brain of the compensation cabinet; it reads cos phi and decides which capacitor step to switch. This page covers its control loop and key settings for stable, oscillation-free operation.
The controller samples CT secondary current and voltage, computes live cos phi and the direction of reactive power, then compares with the target cos phi t such as 0.95. If actual is below, it closes capacitor steps; if met or exceeded it opens them. A switch delay of seconds and a hysteresis band stop chatter so the loop stays stable.
Key settings: target cos phi t near 0.95, never at 1.0 to avoid over-correction; CT ratio matched to the main circuit so displayed current agrees with the clamp; delay long for steady load, short for swing; hysteresis 0.02 to 0.05 to prevent oscillation; step sizes in a 1 2 4 8 ladder for fine approach. Verify CT polarity first or the controller drives the wrong way.
| Parameter | Suggested | Role |
|---|---|---|
| Target PF | 0.92-0.95 | anti over |
| CT ratio | per main | accurate |
| Delay | 2-20 s | anti chat |
| Hysteresis | 0.02-0.05 | no oscill |
| Step | 1/2/4/8 | fine |
| Polarity | check CT | no reverse |
The controller is the brain; set it right and it is stable. First verify CT ratio and polarity, target 0.92 to 0.95, tune delay and hysteresis to the load, and keep step sizes sensible. After run, watch the cos phi trace for a flat, oscillation-free line.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Compensation control follows GB/T 15576 and quality GB/T 12325. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.