The C16 or D16 mark is the trip curve, not the model; wrong choice trips on start. This page explains the C/D difference and selection.
C and D differ only in magnetic instantaneous threshold: C trips at 5~10× rated current In, D at 10~20× In, so D tolerates larger starting surges while C is more sensitive. Their thermal overload curves are essentially the same. On the curve chart, C has its instant zone at 5~10 In, D at 10~20 In.
C suits resistive and lightly inductive loads with small inrush: lighting, sockets, general distribution (offices, homes, control circuits). D suits inductive loads with big starting current: motors, transformers, solenoids, fluorescent ballasts, large capacitors, starting 5~15× rated; a C type would trip on start, so D is mandatory. Traps: fitting C on a motor circuit trips on start; fitting D on pure lighting delays short-circuit protection; mixing confuses selectivity.
After selection read the front print: C16 = 16 A C-curve, D20 = 20 A D-curve. Motor circuits, contactor coils, transformer primaries use D; lighting, sockets, resistive heating use C. Rule: big inrush uses D, steady resistive uses C. Note C/D only affects the magnetic instant zone; overload protection is identical, so do not fix a real overload by switching to D.
| Item | C-curve | D-curve |
|---|---|---|
| Magnetic | 5~10×In | 10~20×In |
| Load | Resistive | Motor inductive |
| Scene | Lighting socket | Motor solenoid |
| Overload | Same | Same |
| Wrong | Start trips | Short delayed |
C trips magnetically at 5~10×In, D at 10~20×In; D tolerates surges. Use C for resistive lighting/sockets, D for motors/transformers/solenoids. C/D only changes the instant magnetic zone; overload is the same. A C type on a motor trips on start.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; MCB per IEC 60898. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.