How the neutral is grounded decides safety and fault behaviour. This page compares IT, TT and TN, their fit and fault traits.
TN systems bond the source neutral directly to earth and connect exposed parts via a protective earth to that point, with TN-S fully separate, TN-C combined and TN-C-S mixed. TT bonds the source neutral to earth but each device has its own local earth electrode, independent of the source. IT leaves the neutral unearthed or high-impedance earthed and the frame is earthed; a first single-phase ground draws tiny current and can keep running.
In TN a ground fault makes a large current and the breaker trips fast, so it is the common safe choice. In TT the fault current is small through two electrodes, so an RCD is usually needed to trip. In IT the first ground fault is tiny and non-interrupting, ideal for hospitals and mines, but a second fault becomes a phase short, so insulation monitoring must alarm.
| System | Neutral | Use |
|---|---|---|
| TN | direct+PE | main plant |
| TT | src+local | outdoor/temp |
| IT | unearthed | hospital/mine |
| TN fault | big trip | fast |
| TT fault | small | needs RCD |
| IT fault | small run | monitors |
Choose the grounding by safety level and continuity need. TN-S is the default; TT must pair with an RCD; IT must have insulation monitoring and no RCD. Keep PE and N strictly separate on site and test electrode resistance on schedule so the earth grid is not decorative.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: System grounding follows GB/T 50065 and shock protection GB/T 16895 with IEC 60364. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.