When the three phases differ too much the motor heats. This page gives the unbalance limit, how negative sequence overheats the motor, and how to rebalance on site.
GB/T 15543 limits the negative-sequence voltage unbalance at the public point to 2 percent in normal operation and 4 percent short term; the motor端 should be tighter. Current unbalance is kept within 15 to 20 percent of the average. Exceeding these stresses motors and drives and is a common overlooked hazard.
Negative-sequence voltage makes a reverse rotating field that induces double-frequency rotor current, adding heat, torque pulsation and vibration. Roughly 2 percent voltage unbalance causes 8 to 10 percent current unbalance and clear temperature rise; at 5 percent output drops and insulation ages fast, cutting life. Measure with a clamp meter and rebalance single-phase loads across the three phases.
| Item | Limit | Harm |
|---|---|---|
| Neg volt | <=2% (4 short) | standard |
| Curr unb | <=15-20% | over heat |
| 2% volt | curr 8-10% | temp rise |
| 5% volt | output down | ages fast |
| Measure | clamp meter | calc dev |
| Fix | spread load | tight joints |
Voltage unbalance is a silent killer. Put three-phase unbalance in routine inspection; act above 2 percent voltage or 15 percent current. Check upstream and joints first, do not swap the motor. Drives are sensitive, so keep the front-end balance tight.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 15543 and machines GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.