How is three-phase power computed and measured. This page gives the general formula and the two-wattmeter versus three-wattmeter methods with their fit.
Regardless of star or delta, total active power is the sum of the three phases and, when balanced, P equals root three times line voltage times line current times cos phi. Reactive Q is root three U line I line sin phi and apparent S is root three U line I line. Note U line and I line are line values and cos phi is per phase; the single formula is easiest when balanced.
The three-wattmeter method uses one meter per phase, voltage coil on that phase to neutral, current coil in that line; it sums directly and is correct for three-wire, four-wire, balanced or not, though it uses more meters. The two-wattmeter method uses only two meters on a three-wire (no neutral) system, P equals P1 plus P2, with current in two lines and voltage across to the third; one reading may go negative and the algebraic sum is the total. Never use two-wattmeter on a four-wire system.
| Method | Fits | Wiring |
|---|---|---|
| Formula | balanced | U line I line |
| 3-meter | 3/4 wire | one per phase |
| 2-meter | wire only | sum of two |
| Unbal | 3-meter ok | 2-meter err |
| 4-wire | no 2-meter | use 3 |
| Reading | may sign | algebraic |
First tell whether the system is three-wire or four-wire. Use three meters for four-wire or unbalanced; two meters save meters on balanced three-wire. A negative reading is normal, sum algebraically. A panel power meter is easiest but know the principle or you cry fault at a negative.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Energy metering follows GB/T 17215 and measurement IEC 61557. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.