Calculating equipment power and estimating distribution capacity

Fifty machines adding up to a large figure does not mean the feeder must carry that figure; demand diversity matters. This page shows how to compute single machine power, apply demand factors, and size transformers and cables without wasting copper.

1. How it works

The active power of one device follows P equals U times I times cos phi for single phase, or the square root of three times U times I times cos phi for three phase; a 15 kW motor at 380 V with cos phi 0.85 draws about 30 A. Installed power is the sum of nameplates, but not everything runs together, so a demand factor Kd applies: the computed load Pc equals Kd times the sum. Machining shops run 0.2 to 0.3, ventilating fans 0.7 to 0.8, and cranes 0.15 to 0.25.

2. Practice and pitfalls

Size the transformer or main switch on apparent power Sc equal to Pc divided by cos phi, then apply a coincidence factor of 0.8 to 0.95 between groups. Example: an installed 200 kW with Kd 0.3 gives Pc 60 kW, and at cos phi 0.8 that is 75 kVA, so a 100 kVA transformer leaves sensible margin. Select cable cross sections from the computed current Ic equal to Pc over the root of three times U times cos phi, never from installed power, or every feeder ends up oversized. Split large single phase loads such as welders and air conditioners evenly across the three phases, keep unbalance under 15 percent, and check the existing transformer loading before adding equipment; above 80 percent loading an upgrade beats nuisance tripping. Keep 20 to 30 percent spare capacity as standing margin.

3. Demand factors for common equipment quick table

Equipment typeDemand factor Kdcosφ
Machining tools0.2 to 0.30.5
Fans and pumps0.7 to 0.80.8
Cranes and hoists0.15 to 0.250.5
Welding machines0.350.6
Lighting0.90.9
Resistance furnaces0.70.95

4. Notes

Size distribution equipment from computed load, not installed nameplate sum. Balance single phase loads across phases and keep 20 to 30 percent capacity margin for growth.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low voltage distribution design follows GB 50054, supply system design GB 50052, with machinery electrical safety per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Sizing cables and breakers from installed power: conductors run oversized and overrated breakers lose protection accuracy
② Leaving large single phase loads unbalanced: beyond 15 percent the neutral shifts and single phase equipment suffers
③ Summing every nameplate without demand factors: the main switch ends up oversized and short circuit settings lose coordination

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.