The third harmonic has a nasty trait: all three phases are in phase, so it piles into the neutral. This page explains why triplen harmonics double or triple neutral current and how to control it.
Harmonics of order 3k, including the third, are zero-sequence: the three phases are in phase, so where the fundamental sums to zero the third adds directly and must return through the neutral. The neutral current becomes the sum of the three third-harmonic currents and can far exceed the phase current.
If each phase carries third-harmonic current I3, the neutral gets 3 I3 in the same direction while the fundamental neutral is zero. Dense LED, switchers and PCs push third harmonic to 30 to 60 percent of phase current, so the neutral totals 1.0 to 1.7 times phase current, far beyond the old design assumption of zero neutral. Thin legacy neutrals overload and burn.
| Item | Fund | 3rd harm |
|---|---|---|
| 3-ph sum | ~0 | 3x in phase |
| Neutral | ~0 | 1.7x phase |
| Source | resistive | LED/SMPS |
| N size | thin ok | thicken |
| Fix | spread | APF/filter |
| Measure | PQ meter | 3rd rate |
Circuits loaded with single-phase rectifiers must size the neutral for possible overload. Retrofits and LED-heavy buildings especially. Measure the third-harmonic content routinely; odd neutral heating points there. Do not let the old no-neutral-current rule kill new loads.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 14549 and harmonic measure GB/T 17626. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.