A thermal relay that is too big never trips and one that is too small trips all day; everything hinges on calculating the motor rated current correctly and sizing the relay to it. This page works the full chain from nameplate to setting, direct-on-line to star-delta.
Start from the nameplate rated current In. For 380V three-phase motors estimate I≈P/(1.732·U·η·cosφ) with η·cosφ near 0.85, which lands at roughly 2A per kW: 7.5kW about 15A, 11kW about 22A, 15kW about 30A. Pick a relay frame whose adjustable range covers the setting with the value near mid-range: a 15A motor takes a 16~25A frame set at 15A. If the plate is missing, estimate from power and confirm with a running-current measurement, investigating anything beyond 10% deviation.
Placement matters: a relay ahead of the motor terminals in a DOL circuit is set to line current In; in a star-delta starter with the relay in the delta leg it carries phase current and is set to 0.58 times In. Large motors use a 5A relay with three current transformers, ratio chosen as In/5, and the setting referred to the secondary: a 140A motor on 300/5 CTs gives 2.3A secondary, set accordingly. Prefer differential three-phase types for phase-loss protection, and never add a bimetal relay inside a variable-frequency drive circuit, where harmonics heat the strip and shift the curve, and the drive electronic overload already does the job.
| Motor power | Rated current | Relay frame | Setting guide |
|---|---|---|---|
| 5.5kW | About 11A | 12~16A frame | Set 11A |
| 7.5kW | About 15A | 16~25A frame | Set 15A |
| 11kW | About 22A | 25~32A frame | Set 22A |
| 15kW | About 30A | 32~40A frame | Set 30A |
| 30kW | About 57A | 63~80A frame | Set 57A |
| 75kW | About 140A | 5A relay + CT 300/5 | Secondary set 2.3A |
Rule: two amperes per kilowatt as a first cut, confirmed by nameplate and measurement; 0.58 in the delta leg; big motors go through CTs with a 5A relay and a secondary calculation; VFD circuits get no bimetal relay. Write the results into the record and check them at every overhaul, because one wrong link skews the whole protection chain.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor and overload relay coordination per GB/T 14048.4 (IEC 60947-4-1); motor performance and currents per the IEC 60034 series; machinery safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.