Common causes and fixes for VFD over-current OC trip

The drive shows OC and a novice just keeps resetting; OC splits into real over-current and false trips. This page lists eight causes and the check order.

1. How it works

The drive measures phase current with Hall sensors and latches the IGBT gate, reporting OC when current exceeds about 1.5× rated for milliseconds, to protect the module. OC is instantaneous over-current, distinct from OL overload which is sustained; OC points to short circuit, too-fast accel or seized load, while OL is long-term imbalance.

2. Numbers and practice

Too-short acceleration pushes start current past 1.5× rated; lengthen to 5~15 s. A seized mechanism drives current to 5~7× rated lock value, so bar the shaft free first. Output short or earth fault from damaged cable or water in terminals trips at start; megger the cable (≥1 MΩ). A faulty module or drifted sensor trips even unloaded and needs repair.

3. Pitfalls and fixes

False trips come from EMI near large starters; add ferrite, shielded cable and separate routing. Over-set torque boost inflates no-load current near the limit; electronic thermal set below 100% rated also trips normal running, raise to 100%~110%. Rule: test unloaded first, then loaded, then at start, and swap a known-good motor lead to locate fast.

4. OC trip troubleshooting

SymptomLikely causeAction
Trips at startShort or earth faultMegger cable and terminals
Trips on accelAccel too shortLengthen to 5~15 s
Trips loaded onlySeized or imbalancedBar shaft, check load
Trips unloadedModule or EMIReplace or shield
Random tripsBoost too highLower to ≤12%

5. Notes

Order: test unloaded, then loaded, then at start; swap a good motor lead to locate fast. Tell OC instantaneous from OL sustained overload. Short-at-start means earth fault; accel trip means time; loaded-only means mechanics.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; protection per GB/T 14048.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Too-short accel keeps tripping OC; lengthen to 5~15 s
② Forcing start on seized load burns the module at 5~7×; free shaft first
③ Excess boost inflates no-load current and false-trips; keep ≤12%

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.