Bigger breaker is not better; too small trips on close, too big fails on short. This page sizes the breaker from load current.
Breaker rated current (trip In) is chosen from the circuit calculated current Ijs: In ≥ Ijs, with up/down coordination. But not too big or overload will not trip. Rule: distribution In is 1.0~1.25× load rated current; motor circuits take 1.5~2.5× motor rated (with D curve to ride start). Resistive slightly larger, inductive leave start margin.
By scene: lighting/socket In≈1.0~1.2× Ijs, e.g. 20 A load → 25 A C. Motor In=(1.5~2.5)×Im with D type, e.g. 10 A motor → 16~25 A D. Cable rule: In must be ≤ cable ampacity or the cable overheats while the breaker stays. Traps: motor In too small trips on start; In above cable ampacity lets the cable burn without tripping; reading power not current misses that same kW differs by poles.
Verify: In ≤ cable ampacity ×0.9; downstream In < upstream with longer upstream time (selectivity). Clamp the real max load current and keep In within 1.0~1.25×, not over-sized. Rule: size by calculated current, check by cable ampacity, margin by start. Record In and cable per circuit for future capacity checks.
| Circuit | In factor | Curve |
|---|---|---|
| Lighting | 1.0~1.2× | C |
| Motor | 1.5~2.5× | D |
| Feeder | 1.0~1.25× | C |
| Cable | ≤ampacity | No burn |
| Up/down | Down| Selective | |
Breaker In is 1.0~1.25× load current, motor 1.5~2.5× with D curve. In must be ≤ cable ampacity or cable burns unprotected. Downstream In below upstream for selectivity. Clamp the max current; do not oversize.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; design per GB/T 50054. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.