After a thermal relay trips, should someone press reset, or should it recover on its own? The wrong choice leaves a line stopped with nobody around, or worse, restarts a machine whose fault is still there. This page compares the two reset modes and how to switch and apply them.
Manual reset keeps the NC contact open after tripping until a person presses the reset button, so the machine cannot restart before the cause is found; it suits important equipment and unattended areas. Automatic reset closes the contact again once the bimetal cools, typically 2~5 minutes after the trip, fitting auxiliary equipment such as exhaust fans where an unattended restart is harmless. The front knob or lever switches between AUTO and MANUAL, and many models offer remote-reset terminals for a button in the control room.
Switch the mode only with the relay tripped or de-energised, and before choosing AUTO confirm that a restart endangers nobody, which is why standards lean toward manual. After any reset, wait 1~2 minutes so the windings shed heat before restarting; trip-reset-restart cycles two or three times in a row often kill the motor on the third start, because repeated inrush heats the windings harder than one steady overload. Route reset authority to people who understand the fault, and log every reset in the shift record.
| Mode | Recovery | Suitable | Risk |
|---|---|---|---|
| Manual | Press reset button | Key equipment, unattended areas | Line waits for a person |
| Automatic | Cooling 2~5 min | Fans and auxiliaries | Restart with fault present |
| Remote | Button on terminals | Control-room operation | Authority must be controlled |
| After reset | Wait 1~2 min to cool | All cases | Repeated restarts burn motors |
| Mode switching | Tripped or dead | AUTO/MANUAL knob | Unreliable when live |
| Fault handling | Find cause before reset | Iron rule | Forced restarts destroy motors |
Rule: manual reset for anything important, automatic only for harmless auxiliaries; find the cause before resetting and leave cooling time before restarting; safety circuits never recover automatically. Write the reset mode and its authority into the procedure, log resets per shift, and keep the fault history traceable.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Reset modes and overload protection per GB/T 14048.4 (IEC 60947-4-1) and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.