A burning main terminal is usually a wiring fault, not a bad contactor. Left alone it welds and fires. Here are the causes and the torque fix.
Main-terminal heat almost always comes from too-high contact resistance: low screw torque, no crimp terminal, stray strands, direct copper-aluminium oxide, debris on the face. Current through that high resistance makes P=I²R heat, local rise, a loop where oxidation grows resistance. The contactor is fine; one loose terminal alarms the whole machine. A 380V/30A terminal with low torque can exceed 60K rise.
Fix de-energised and proved dead. Locate the hot point by infrared or back-of-hand, open the terminal and inspect: is the crimp sound, any stray burn, oxide on the face. Re-torque to spec (moulded-case main about 3.5~5N·m, smaller about 2.0~2.5N·m), dress oxide or change the terminal, always crimp OT/UT on stranded wire with no stray. Add a transition terminal for Cu-Al.
Pit one: tightening live, arc flash and shock. Pit two: stranded wire thrust in with no crimp, stray strands give high resistance and sparking. Pit three: only tightening, not cleaning oxide, it heats again. De-energise and prove dead, crimp properly, torque to spec, clean the face, then infrared re-check with phase difference under 15%.
| Item | Cause | Fix |
|---|---|---|
| Torque | Low / loose | Spec N·m |
| Wire | Strand no crimp | Crimp OT/UT |
| Oxide | Face poor | Dress / change |
| Cu-Al | Direct oxide | Transition |
| Stray | Bad bond | Re-crimp |
| Re-check | IR diff | <15% pass |
Rule: main-terminal heat is mostly high contact resistance; de-energise and prove dead, crimp properly, torque to spec, clean the face, transition for Cu-Al. After fix infrared re-check difference under 15%, no live tighten, no stray strands.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Temperature rise and terminals per GB/T 14048.1, contactor per GB/T 14048.4, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.