Too short trips the drive, too long slows the line. This page shows how to size both from load inertia and cycle time.
Acceleration time is how long the drive takes from 0 Hz to max frequency, deceleration the reverse, in seconds. It is not the motor physical limit but how fast you allow frequency to change. Short times spike current and trip OC; long times slow the cycle on high-inertia loads. Small motors up to 7.5 kW use 3~10 s, large fans 30~60 s. Short deceleration pumps regenerative voltage and trips OV unless a brake is fitted.
Roughly t ≈ J×Δn / (9.55×T_allow). A 30 kW fan with J≈2 kg·m² at 1480 r/min and allowed torque 1.2× rated (≈230 N·m) gives t≈1.35 s; take 3× margin to 5 s. For deceleration, if t<2 s without brake resistor the DC bus can exceed 700 V and trip. Start long, then shrink by 20% steps while watching current and bus voltage.
Debug rule: set both times long (e.g. 30 s), confirm no trip, then compress. A fan at 1 s deceleration trips OV3; extend to 10 s or add braking. A conveyor at too-short acceleration trips OC above 1.5× rated; raise to 8 s. Enable S-curve to soften mechanical shock on start and stop.
| Load type | Accel time | Decel time |
|---|---|---|
| Pump ≤7.5 kW | 3~10 s | 3~10 s |
| Conveyor 15~30 kW | 5~15 s | 5~15 s |
| Large fan | 30~60 s | 20~40 s |
| Hoist | 3~8 s brake | 1~5 s |
| Big inertial centrifuge | 60~120 s | Need brake resistor |
Start long, then compress 20% at a time while watching current and bus voltage. Lengthen acceleration for heavy start, add braking for big inertia deceleration. S-curve reduces mechanical shock.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; motor starting per GB/T 21207. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.