Setting acceleration and deceleration time on a VFD

Too short trips the drive, too long slows the line. This page shows how to size both from load inertia and cycle time.

1. How it works

Acceleration time is how long the drive takes from 0 Hz to max frequency, deceleration the reverse, in seconds. It is not the motor physical limit but how fast you allow frequency to change. Short times spike current and trip OC; long times slow the cycle on high-inertia loads. Small motors up to 7.5 kW use 3~10 s, large fans 30~60 s. Short deceleration pumps regenerative voltage and trips OV unless a brake is fitted.

2. Numbers and practice

Roughly t ≈ J×Δn / (9.55×T_allow). A 30 kW fan with J≈2 kg·m² at 1480 r/min and allowed torque 1.2× rated (≈230 N·m) gives t≈1.35 s; take 3× margin to 5 s. For deceleration, if t<2 s without brake resistor the DC bus can exceed 700 V and trip. Start long, then shrink by 20% steps while watching current and bus voltage.

3. Pitfalls and fixes

Debug rule: set both times long (e.g. 30 s), confirm no trip, then compress. A fan at 1 s deceleration trips OV3; extend to 10 s or add braking. A conveyor at too-short acceleration trips OC above 1.5× rated; raise to 8 s. Enable S-curve to soften mechanical shock on start and stop.

4. Reference acceleration and deceleration times

Load typeAccel timeDecel time
Pump ≤7.5 kW3~10 s3~10 s
Conveyor 15~30 kW5~15 s5~15 s
Large fan30~60 s20~40 s
Hoist3~8 s brake1~5 s
Big inertial centrifuge60~120 sNeed brake resistor

5. Notes

Start long, then compress 20% at a time while watching current and bus voltage. Lengthen acceleration for heavy start, add braking for big inertia deceleration. S-curve reduces mechanical shock.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; motor starting per GB/T 21207. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Fan deceleration at 1 s trips OV; extend to 10 s or add brake
② Conveyor acceleration too short trips OC; raise to about 8 s
③ No S-curve gives hard mechanical shock; enable S-curve

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL