Residual current breaker versus ordinary breaker

An ordinary breaker only handles over-current; leakage that kills passes undetected. This page explains how an RCD differs and how to fit it.

1. How it works

An ordinary MCB senses only over-current through itself (overload, short) and does not care where current goes, so if live leaks to earth or a person is shocked, as long as total current stays under rating it will not trip. A residual current device (RCCB/RCBO, RCD) adds a zero-sequence current transformer comparing live and neutral vector sum; if the difference (residual) exceeds threshold (30 mA home, 100~300 mA industrial) it trips within ≤0.1 s, specifically against shock and earth fault.

2. Numbers and practice

An MCB protects overload plus short (over-current dimension). The RCD adds residual current protection on top; an RCBO combines both in one. RCD parameters are trip current and time: 30 mA/0.1 s is the shock-protection standard, above 100 mA mostly for fire or equipment. Note an RCD prevents leakage but not overload; a pure RCCB still needs an MCB in series for short circuit.

3. Pitfalls and fixes

Fit: socket circuits, wet areas (bathroom, shop pits) and mobile equipment must have 30 mA RCD; main inlet may have 300 mA fire RCD. Traps: using an MCB instead of RCD fails to trip on shock and kills; RCD must be tested monthly with the button or you miss failure; three-phase RCD neutral must pass the transformer and not be re-grounded or it mis-operates or fails; sensitive 30 mA on VFD leakage loads trips often, raise threshold or isolate. Rule: shock protection needs RCD, over-current needs MCB, they complement.

4. RCD vs ordinary

ItemOrdinaryRCD
ProtectOver/shortPlus leakage
SenseOver-currentResidual
ShockNone30 mA/0.1 s
BuildBimetal+coilPlus ZCT
Must fitAllSocket wet mobile

5. Notes

Ordinary breakers block over-current not leakage shock; RCD senses residual current (30 mA/0.1 s for shock) and trips within 0.1 s. RCBO merges both. Sockets, wet and mobile sites need 30 mA RCD, test monthly. Sensitive RCD on VFD leakage trips often.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; RCD per GB/T 16916 / IEC 61008. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① MCB instead of RCD fails to trip on shock
② RCD not tested monthly hides failure
③ Three-phase RCD neutral not through transformer mis-trips

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.