X and Y safety capacitors at the supply input

X caps bridge L-N (differential, fail short → fuse); Y caps go line-to-earth (fail short → shock hazard).

1. How it works

Y-cap size is capped by touch current: I=2πfCU; medical gear allows only ~0.1mA, hence 1~4.7nF typical.

2. Practice and pitfalls

Always certified parts (X1/X2, Y1/Y2), never generic ceramics; keep the X-cap discharge resistor.

3. X/Y comparison

AspectX capacitorY capacitor
ConnectionAcross L-NLine/N to earth
FiltersDifferentialCommon mode
FailureShort → fuseShort → live earth
ClassX1/X2/X3Y1/Y2
Typical size0.01~1μF1~4.7nF
ConstraintDischarge resistorTouch current

4. Notes

Apply the points above to X and Y safety capacitors at the supply input; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 14472, IEC 60384-14, GB 4943.1, GB 4706.1 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Substituting generic caps for Y class
② Omitting the X-cap bleeder
③ Copy-pasting Y values into medical devices

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.