A breaker with burning terminals or a soft case is not a small matter; poor contact is brewing a fire. Once temperature rise passes the limit it must be dealt with.
A breaker heats in service; the standard caps terminal temperature rise at 60K above ambient, with limits also on the enclosure. At 40℃ ambient the terminal may reach about 100℃, hot to touch but at the edge. Once rise stays above 60K or the case deforms and smells burnt, it is a pre-failure sign. The heat comes from I-squared-R loss and contact resistance; one high-resistance joint overheats locally, the most common electrical fire start.
Causes: first, terminal screw torque too low or loosened by thermal cycling, contact resistance shoots up (typical 2.0~2.5N·m miniature, 3.5~5N·m moulded case). Second, undersized wire carrying more than its rating, heating the whole run. Third, chronic overload above rating. Fourth, direct copper-aluminium joint oxidising. Fifth, worn internal contacts or carbon in the arc chute raising internal resistance.
The common mistake is simply fitting a bigger breaker; the rise drops but the wire is still thin and the screw still loose, so it burns later. Instead, de-energise, verify, then measure torque, check wire size and read actual current with a clamp meter. Clean oxidation, torque to spec, tin or change the terminal as needed. Tightening live is suicide; cut power and prove dead first.
| Item | Limit / sign | Action |
|---|---|---|
| Terminal rise | ≤60K | Above, check contact |
| Screw torque | 2.0~2.5N·m MCB | Torque to spec |
| Wire size | Rating ≥ load | Upsize wire |
| Actual current | ≤ rated | Reduce or uprate |
| Cu-Al joint | No direct bond | Transition terminal |
| Smell/deform | Switch off now | Internal fault, replace |
Rule: rise above 60K is an alarm, measure torque and current first, do not just upsize. De-energise and prove dead, torque to spec, upsize wire if short, add transition for Cu-Al. Infrared scan monthly and kill hot spots early.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Temperature-rise limits per GB/T 14048.1, breaker product per GB/T 14048.2, wiring design per GB/T 16895 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.