Power factor control and phasing operation of synchronous motors

The most valuable trick of a synchronous motor is acting as a reactive source; over-excitation makes it emit capacitive vars. This page explains the phase-control principle, the V curve, and field practice of compensating power factor.

1. How it works

Power factor is set by rotor excitation: under-excited it draws lagging reactive power, over-excited it supplies leading reactive power like a capacitor, adjustable continuously from lagging to leading, something induction motors cannot do. At fixed real power the stator current versus field current is a V curve: minimum current at unity power factor normal excitation, lagging on the under-excited side and leading on the over-excited side.

2. Practice and pitfalls

Plants run large synchronous drives slightly over-excited so they both carry load and export reactive power, raising bus voltage and saving capacitor banks. Adjust manually or by closed-loop power-factor control on the exciter, but over-excitation is capped by rotor heating and stator iron loss, and under-excitation by stability. Keep the power-factor meter near 0.95 leading for economy; too much over-excitation drives terminal voltage too high.

3. Power factor regulation and condenser operation of synchronous machines

ExcitationPower factorReactiveState
UnderexcitedLaggingAbsorbingNot preferred
Normal=1ZeroBaseline
Light overexcitedLeadingExportingEconomical
Strong overexcitedStrongly leadingExporting moreTemp limited
At the limitPast limitsHazardousForbidden

4. Notes

A synchronous machine sweeps its power factor from lagging to leading just by trimming excitation; overexcited, it exports capacitive vars exactly like a capacitor bank. The bottom of the V-curve is cos phi = 1 at normal excitation, with the leading side on the right. Plants run big synchronous motors lightly overexcited so they do work while supplying vars, but rotor temperature rise caps the overexcitation, and around 0.95 leading is the economical setpoint.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Synchronous machines: GB/T 755 / IEC 60034-1; power quality: GB/T 12325. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Unbounded overexcitation pushes rotor temperature past its class and ages the insulation
② Expecting an induction motor to trim power factor: it has no such knob at all
③ Confusing underexcitation with overexcitation imports vars instead of exporting them and earns the penalty

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.