A relay that trips all day while the motor feels cool is not protecting anything; the cause is usually setting, wiring or environment, not real overload.
First split real overload from false trips. Clamp the three phases with a current meter and compare with nameplate In. If current is symmetric and steady above 1.1 times In, the load is genuinely overloaded. If current stays at or below In yet the relay still trips, it is a false trip. Check whether the setting dial has been moved off the marked position, and whether the panel temperature exceeds 40℃, because every degree above that advances the trip characteristic by roughly 1%.
Wiring faults are easy to miss. Loose main-terminal screws (thermal relay about 2.0~2.5N·m) raise contact resistance and extra heat trips the bimetal; terminals above 60K by infrared should be retightened. Mounting the relay hard against the contactor lets the contactor heat bake it, so leave 10~20mm or a barrier. In star-delta circuits a relay placed in the delta loop must be set to 0.58 times In. Ageing bimetals drift after years of cycling, and relays behind a VFD suffer harmonic heating, so replace old units and let the drive do electronic protection.
| Cause | Symptom | Check | Action |
|---|---|---|---|
| Setting drift | Trips at normal current | Dial off mark | Reset and mark |
| High ambient | Worse in summer | Panel >40℃ | Correct setting |
| Hot terminals | Rise >60K | Loose torque | Tighten 2.0~2.5N·m |
| Baked by contactor | Near contactor | Too close | Gap 10~20mm |
| Harmonics | Trips on VFD | Relay after drive | Use electronic protect |
| Aged element | Value drift | Many years | Replace relay |
Rule: meter first to tell real from false, then setting and environment, then wiring and element. Do not just raise the setting; that hides the fault. Log every check in the equipment file and make setting, mounting gap and panel temperature part of routine inspection.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Trip behaviour and coordination per GB/T 14048.4 (IEC 60947-4-1) and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.