The T-n curve of an induction motor carries four key points, and reading them tells you whether the machine will actually drive your load. This page names the synchronous, rated, maximum torque and starting points with their typical numbers.
The mechanical characteristic is torque against speed and it marks four points. The synchronous point at n0 has slip zero and zero torque, the ideal no load. The rated point at nN carries rated torque TN with slip 2 to 5 percent. The maximum torque point at critical slip sm of about 10 to 20 percent is the overload ceiling. The starting point at standstill carries starting torque Tst. Rated torque is 9550 times PN over nN in the usual units, and these four points split the curve into a stable working region and an unstable one where the load must not sit.
Numbers matter. Maximum torque ratio Tmax over TN runs 2 to 2.5, starting torque ratio Tst over TN about 1.5 to 2.2, with high start types reaching 2.5. Critical slip sits at 0.1 to 0.2, near 0.8 to 0.9 of n0. Because torque scales with voltage squared, a 10 percent voltage drop cuts Tmax by roughly 19 percent. In the field, keep the worst load torque below Tmax with a 1.5 to 2 times margin, overlay the load curve on the motor curve and confirm the crossing lies on the stable descending side; a long start or slow current decay usually means the load nears Tst, so check the mechanism before blaming the motor.
| Key point | Slip s | Torque feature | Typical value |
|---|---|---|---|
| synchronous | 0 | zero torque no load | n0 60f over p |
| rated | 2 to 5 pct | rated torque TN | TN 9550 PN over nN |
| max torque | 10 to 20 pct | overload ceiling | 2 to 2.5x TN |
| starting | 100 pct | start torque Tst | 1.5 to 2.2x TN |
| stable region | 2 to 5 pct | rated torque near | daily work point |
The four points set the capability envelope. Keep load below Tmax with margin and remember low voltage squares down the maximum torque. When start is slow, suspect the mechanical load near Tst before swapping the motor, and always place the operating point on the stable side.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rating per GB/T 755 (IEC 60034-1); test method per GB/T 1032. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.