A wrongly set thermal relay either trips all day or never trips at all. The setting is not a guess off the nameplate; it is calculated from the motor rated current and site conditions. This page covers the calculation, the dial and the verification.
The reference is the motor nameplate rated current In, never the contactor or breaker rating. General duty takes 0.95~1.05 times In; long-start or heavy duty takes 1.05~1.2 times with a higher trip class; above 40℃ ambient reduce the setting by about 1% per degree, calculated at the panel temperature, not outdoors. Keep the setting near the middle of the adjustable range, because values hugging the ends give unstable behaviour.
Turn the dial to the calculated value, then verify dead: press the test button and confirm the contacts and indicators. Verify live: run the motor, measure the actual current, and recalculate if it deviates more than ±10% from the setting. In a star-delta starter with the relay in the delta circuit the winding carries phase current, so the setting is 0.58 times In, the single most common mistake on site; only a relay in the main path uses In. Record every setting, mark the dial after commissioning, and recheck on rounds for tampering.
| Case | Factor | Example 15A motor | Caution |
|---|---|---|---|
| General duty | 0.95~1.05 x In | 14~16A | Baseline method |
| Heavy, long start | 1.05~1.2 x In | 16~18A | Higher trip class |
| High ambient | Minus 1% per °C above 40 | Use panel temp | Correct before setting |
| Star-delta delta leg | 0.58 x In | About 8.7A | Most common error |
| Motor replaced | Recalculate from new plate | — | Update the record |
| Verification | Compare running current | Within ±10% | Reset if beyond |
Rule: set from the motor nameplate, not the contactor; multiply 0.58 in the delta leg; correct for heat; verify after setting. The value and the dial mark go into the record, rounds check for drift, and any component change forces a recalculation.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Setting and characteristics per GB/T 14048.4 (IEC 60947-4-1); motor protection coordination per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.