Jog means move only while held, continuous means run on after one press; the only difference is the self-hold. Here are the two circuits and where they fit on site.
A jog (inching) circuit has no self-hold: the start NO button sits directly in the coil loop, hold it and the coil energises and the motor turns, release and the loop opens, coil drops, motor stops. It suits fine positioning, nudging material and manual finding. Each time is by hand, so there is no hold contact and no risk of staying energised, but it is tiring and needs a hand on the button.
Continuous run adds the contactor own NO 13-14 across the start button as self-hold; after pressing, 13-14 keeps the coil and the motor runs until the stop NC is pressed. The only hardware difference from jog is whether the self-hold contact is in. Same contactor: bridge 13-14 across the start and it is continuous, remove it and it is jog.
Pit one: a jog device wrongly gets self-hold, release the button and it still turns, hurting work or people during alignment. Pit two: a continuous device with poor self-hold jogs one press at a time, unstable production. Pit three: a latching-type button used as plain jog button, mis-operation. Confirm the process needs jog or continuous, fit or remove the hold contact accordingly, verify by hand that release stops or holds.
| Item | Jog | Continuous |
|---|---|---|
| Self-hold | None | Own 13-14 |
| Operation | Hold to move | Press, runs on |
| Stop | Release stops | Stop button |
| Use | Align, find | Long run |
| Risk | Tiring | Wrong hold danger |
| Hardware | No hold | Bridge = cont. |
Rule: jog is hold-to-move with no self-hold, continuous bridges own NO for latching. Same contactor, with or without 13-14 is the two modes. Verify on test that release stops (jog) or holds (continuous), pick by process.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit per GB/T 14048.5, contactor per GB/T 14048.4, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.