Principle of reactive compensation and capacitor sizing

Reactive compensation means paralleling capacitors so their leading VAR cancels the lagging VAR of motors and transformers, lifting cos phi. This page gives the principle and the Qc formula to size the bank in one step.

1. How it works

Inductive loads make lagging reactive power; a capacitor draws current 90 degrees ahead and emits leading VAR that cancels it, shrinking total Q and apparent S so cos phi rises. The load then supplies its own reactive need locally instead of pulling it from the generator through the lines, cutting loss and drop.

2. Practice and pitfalls

To move from cos phi1 to cos phi2 the needed capacity is Qc equals P times tan phi1 minus tan phi2, with P in kW. For 100 kW from 0.70 to 0.95, tan goes 1.020 to 0.329 so Qc is about 69 kvar, rounded to 75 in groups. From 0.80 the need drops to about 42 kvar. Rate capacitors at 450 V on a 400 V system and series a 7 percent reactor against fifth-harmonic resonance.

3. Compensation sizing reference

CaseParamsQc
P100 0.70-0.95tan1.020/0.32969.1 kvar
P100 0.80-0.95tan0.750/0.32942.1 kvar
P200 0.75-0.95tan0.882/0.329110.6 kvar
Grouping75 kvar 5 grp10-20 each
Rating400 V sys450 V cap
Reactorvs 5thseries 7 pct

4. Notes

Compute Qc by P times the tan difference in one step and group the bank with margin. Before building, total the active power and current factor, then set total kvar, and after run watch the factor meter to add or shed steps without overshooting.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Compensation design follows GB/T 15576 and quality GB/T 12325. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Under-compensation leaves factor below 0.90 and still fined
② Over-correction turns capacitive and resonates, also fined
③ No reactor lets fifth-harmonic resonance burst the capacitor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.