Breaking capacity of a circuit breaker: meaning and choice

The 6 kA or 10 kA mark is not current size but the fault current it can clear. This page explains how to compute and choose breaking capacity.

1. How it works

Breaking capacity Icu/Ics is the maximum fault current (kA) the breaker can safely clear; above it contacts weld or the case bursts. The actual short-circuit current Ik at the mounting point must be ≤ breaking capacity. Ik comes from transformer size and impedance: Ik≈S/(√3·Uk·U); e.g. 500 kVA, Uk=6%, 400 V gives Ik≈12 kA. So the low-voltage incoming side needs at least 25 kA.

2. Numbers and practice

Icu (ultimate) is the max current cleared once, possibly damaged after; Ics (service) is cleared repeatedly and remains usable, typically 25%~100% of Icu. Domestic MCBs mark Icn≈6 kA; industrial MCCBs mark Icu/Ics like 35/25 kA. Choose by the point prospective short-circuit current: end circuits with small Ik use 6 kA MCBs, busbar side needs high breaking.

3. Pitfalls and fixes

Steps: compute Ik at the point; pick breaking capacity ≥ Ik×1.2; coordinate up/down so upstream ≥ downstream and acts faster or current-limits. Traps: a 6 kA MCB at a near-transformer point with large fault bursts; reading only current rating ignores breaking and fails on short; a 4.5 kA domestic MCB in an industrial cabinet is insufficient. Rule: compute short current first, then breaking; if short, use higher break or add current limitation.

4. Breaking capacity choice

PointIkPick
End1~3 kA6 kA MCB
Feeder5~10 kA10~25 kA
Incoming10~20 kA≥25 kA
Near XFMR>20 kAHigh+limit
Icu/IcsIcs reuseIcu once

5. Notes

Breaking capacity is the max safe fault current; the point Ik must be ≤ it. Compute Ik (500 kVA/6%/400 V≈12 kA) then pick ≥Ik×1.2. End circuits use 6 kA, busbar ≥25 kA. Ics is reusable, Icu once only.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; short-circuit per GB/T 50054. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① 6 kA MCB near transformer bursts on large fault
② Reading only current rating ignores breaking on short
③ 4.5 kA domestic MCB in industrial cabinet insufficient

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.