Direct start capacity limit and grid impact

Small motors direct on line are simplest but a large motor direct start drops the whole line voltage instantly. This page explains the capacity limit and how to compute voltage drop so the lights do not dim across the plant.

1. How it works

Why limit capacity: direct start current is 6 to 8 times rated and this surge through transformer impedance and line impedance causes a voltage drop making the bus voltage plunge. Rule of thumb: single motor power not exceed 20 to 30 percent of supply transformer capacity to allow direct start; frequent start take the lower limit. Example: 100 kVA transformer direct start motor suggest at or below 20 kW or voltage drop exceeds 15 percent tripping neighbours.

2. Numbers and practice

Voltage drop computation: delta U percent approximately equals start current over rated times transformer short circuit impedance percent times motor capacity over transformer capacity. Allowance: frequent start at or below 10 percent occasional at or below 15 percent. Example: 30 kW motor about 60 A start 7 times 420 A on 250 kVA transformer short circuit impedance 4 percent gives delta U about 7 times 4 percent times 30 over 250 about 3.4 percent qualified. Exceed means soft starter autotransformer or inverter.

3. Pitfalls and fixes

Pit one: computing only motor power forgetting other existing load on the transformer total drop exceeds. Pit two: long feeder impedance doubles the end drop. Pit three: assuming inverter output side also limited while inverter start current is small and not limited. Rule: compute delta U percent see if at or below 15 percent occasional 10 frequent; if over add soft starter autotransformer inverter or thicken cable and adjust transformer tap.

4. Direct start capacity limit table

ConditionLimitFormulaConsequence
Rule<=20~30% xfmrsingle/totalelse drop
Drop<=10~15%Ik Uk% Sm/Stneighbour trip
Frequentlower 20%count totallights dim
Motor size≤7.5~11 kWVs trafoSoft start above
Distanceend doublesthicken cabledrop doubles

5. Notes

Single direct start motor not exceed 20 to 30 percent of transformer capacity and delta U percent equals start current over rated times Uk percent times motor over transformer capacity must be at or below 15 percent occasional 10 frequent; exceed means soft starter autotransformer inverter and thicken long cable.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Voltage deviation see GB/T 12325 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Computing only motor forget other load total drop exceeds
② Long feeder impedance doubles the end voltage drop
③ Assuming inverter output also limited while start current small

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.