Siemens 5SY breaker parameters and selection

The 5SY is the European MCB representative with marking slightly different from Schneider. This page decodes its key parameters and how to choose.

1. How it works

The 5SY family covers 5SY (6 kA) and 5SY4/5SY6 (10 kA), current 0.3~63 A, 230/400 V, to IEC 60898 / GB/T 14048.2. Breaking class sits in the model suffix (5SY4 is 10 kA). Poles 1P~4P. Like the iC65, pick the class by the point short-circuit current: end circuits use 6 kA, near-transformer or feeders use 10 kA. Curves are C/D plus K (10~14 times for transformers and solenoids) and B (3~5 times for fluorescent inrush); motors use D or K.

2. Practice and pitfalls

Selection flow: compute load current for In (1.0~1.25 times resistive, 1.5~2.5 times motor), choose curve by load, breaking class by fault point, poles by circuit, and snap on a 5SV residual module (30 mA for persons, 100/300 mA for fire) as needed. Traps: 10 kA at end wastes money while 6 kA at a big fault point is unsafe; all-C trips motors on start; the 5SV neutral must pass the sensor and not be re-grounded or it mis-trips. Rule: breaking to point, curve to load, poles to circuit, RCD to place.

3. Siemens 5SY selection

PointValueNote
Breaking5SY 6kA / 5SY4 10kABy fault
CurveC/D/K/BBy load
Current0.3~63 ABy load
Poles1P~4P2P single
RCD5SV module30/100/300 mA

4. Notes

For 5SY, set breaking class by the fault point (6 kA end, 10 kA feeder), curve by load (C resistive, D/K inductive), poles by circuit, and add a 5SV RCD (30 mA for persons) on wet or mobile circuits. All-C trips motors, and wrong breaking class is either wasteful or unsafe. Verify 3C and breaking marking on arrival.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; MCB per IEC 60898. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① 10 kA at end wastes; 6 kA at big fault unsafe
② All-C trips motors on start
③ 5SV neutral mis-wired or re-grounded mis-trips

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.