Opening a contactor coil, that big inductor kicks a high voltage that pits contacts and upsets the PLC. A parallel RC snubber (or diode) bleeds that spike. Here is the principle, values and wiring.
A coil is an inductor, current cannot jump. At opening the field collapses and induces a back-EMF far above supply, hundreds of volts, that travels the control wire, arcs the control contacts, disturbs the PLC and nearby low-power circuits, even punches the driving transistor. AC coils are easier at current zero, but DC coils, especially transistor-driven, spike harder and must be snubbed.
A resistor-capacitor in parallel across the coil gives the collapse a path at opening; the capacitor takes the energy, the resistor limits current and dissipates it, clamping the spike low. Typical R 100~220Ω, C 0.1~0.47µF, voltage rating ≥250VAC or 400VDC. AC coils may use a MOV; DC coils commonly use a reverse free-wheel diode (e.g. 1N4007). Too large an RC can slow pick-up.
Pit one: a DC coil diode reverse-polarised (cathode to positive), it shorts the coil and burns the driver. Pit two: a snubber capacitor rated too low bursts on the spike. Pit three: the RC put across the supply, not the coil, doing nothing. Connect across the coil ends, DC diode reversed, values by coil voltage, reduce C if pick-up suffers.
| Item | Value / wire | Effect |
|---|---|---|
| Resistor R | 100~220Ω | Limit, dissipate |
| Cap C | 0.1~0.47µF | Give a path |
| Rating | ≥250VAC/400V | No burst |
| DC | Reverse diode | Free-wheel |
| AC | RC or MOV | Clamp spike |
| Position | Across coil | Not supply |
Rule: the coil kick at opening needs an RC (100~220Ω, 0.1~0.47µF) or a reverse DC diode across the coil. Rate with margin, connect at the coil ends not the supply, never reverse the diode. Reduce C if pick-up suffers.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear and control per GB/T 14048.5, EMC immunity per GB/T 17626 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.