Power, voltage and current on the plate are enough to size wiring, but many mix input and output. This page explains their relation and how to pick wire and breaker.
Rated power Pn is mechanical output at the shaft (kW), not input; rated voltage Un is line voltage (380 or 660 V three-phase); rated current In is what the grid supplies at full load. They link through efficiency η and power factor cosφ: input Pin = Pn/η ≈ √3·Un·In·cosφ, so In = Pn/(√3·Un·η·cosφ). Example 15 kW, η=0.9, cosφ=0.85, 380 V gives In≈29.9 A.
Size wire by In, not power: 29.9 A needs 6 mm² copper (about 32~40 A rating) with margin; breaker at 1.2~1.5× In, i.e. 36~45 A. Voltage sets connection: 380 V uses Δ, 660 V uses Y on dual-voltage motors. Traps: using 2 A/kW rule undersizes for low-cosφ inefficient motors; wiring a 660 V motor to 380 V leaves too little torque; ignoring 5~7× start current when sizing the breaker trips it.
After sizing, check the cable current table: does 6 mm² derated in conduit still exceed In×1.1? For VFD use, pick the drive current class by In. If the plate is模糊, measure no-load current about 0.2~0.5 In; larger means aging or mechanical tightness. Power is output, current is input, voltage sets connection; solve all three together. Keep a clamp meter; if measured In differs from plate by >10%, investigate.
| Use | Basis | Formula |
|---|---|---|
| Wire | Rated In | In×1.1 table |
| Breaker | 1.2~1.5×In | 30A→36~45A |
| Current | Pn/(√3Unηcosφ) | 15kW≈30A |
| Connection | Voltage Un | 380Δ/660Y |
| VFD class | By In | ≥In |
Size wire by rated current not power; breaker 1.2~1.5× In. Three-phase current In=Pn/(√3·Un·η·cosφ). Voltage sets Δ/Y, do not reverse on dual-voltage. If measured In differs >10% from plate, investigate.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; distribution per GB/T 14048.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.