Star-delta starting needs three contactors working in sequence; wrong order gives full-voltage shock or a short. Here are KM1/KM2/KM3 roles, sequence and cautions.
Star-delta uses main KM1, star KM2 and delta KM3. KM1 stays in for mains. At start KM2 pulls in and shorts the winding tails into star, reduced voltage start (each phase 220V, low current). After a few seconds KM2 drops and KM3 pulls in, winding to delta, full voltage (each phase 380V). KM2 and KM3 must interlock or both-in shorts the winding.
Sequence: press start, KM1 in, KM2 in (star), time (usually 3~8s by load speed), KM2 out, KM3 in (delta). Leave tens of milliseconds gap (by interlock) so KM2 is out before KM3 in, avoiding phase short. The timer must let the motor near rated speed; too short a jolt, too long star overheats.
Pit one: no KM2/KM3 interlock, both pull in at switch, winding tails shorted, explosion. Pit two: KM3 delta phase wrong, motor reverses or draws heavy. Pit three: thermal relay on the star side, setting mismatched at delta run. Fit KM2/KM3 electrical plus mechanical interlock, check phase, set thermal by delta current, tune delay to load.
| Role | Contactor | State |
|---|---|---|
| Main | KM1 | In throughout |
| Star | KM2 | In at start |
| Delta | KM3 | In at run |
| Interlock | KM2↔KM3 | Never both |
| Delay | Timer relay | 3~8s |
| Thermal | By delta I | Set match |
Rule: KM1 mains, KM2 star, KM3 delta, KM2/KM3 double interlock never both-in. Gap at switch, delay by speed, thermal set by delta current, check phase to avoid reverse.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor starter standard per GB/T 14048.4 and GB/T 14048.6, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.