Current rating is not enough; the breaker must survive lightning and switching overvoltages. Uimp and the overvoltage category set the insulation level.
Rated impulse withstand voltage Uimp is the 1.2/50μs lightning peak the breaker survives without breakdown, in grades 4kV, 6kV, 8kV, 12kV. It shows insulation strength and links to the installation overvoltage category CAT Ⅰ~Ⅳ: the incoming distribution is CAT Ⅳ and needs high Uimp, in-equipment is CAT Ⅱ. Too low a Uimp lets induced lightning or switching surges punch through the internal clearances and cause phase-to-phase short.
Also read rated insulation voltage Ui and pollution degree (1~4, workshops usually 3). Creepage and clearance grow with Ui and pollution; at Ui 400V and pollution 3 the minimum creepage is about 4~6mm. Keep phase-to-phase and earth air gaps in the cubicle, do not overpack the rail or let dust and oil build up, or the creepage is bridged and coordination fails.
Pit one: to save cost the incoming breaker is downgraded from 8kV to 4kV Uimp, a thunderstorm kills it and the downstream too. Pit two: thick dust and oil mist shorten the real creepage, fine until a surge strikes. Pit three: mixing categories without isolation lets high-category surges ruin low-category gear. Choose CAT and Uimp by position and keep clean gaps.
| Item | Common grade | Note |
|---|---|---|
| Uimp | 4/6/8/12kV | Higher resists surge |
| Overvolt cat | CAT Ⅰ~Ⅳ | Incoming is CAT Ⅳ |
| Pollution | 1~4, shop 3 | Higher needs gap |
| Ui | ≥ line voltage | Pairs with Uimp |
| Creepage | Ui400V ~4~6mm | Grows with pollution |
| Mounting | Gaps, keep clean | Stop creepage bridge |
Rule: incoming breaker high Uimp (≥8kV) and CAT Ⅳ, in-equipment may drop. Ui not below line voltage, pollution by site, creepage generous, cubicle clean with air gaps, no dust-oil bridge.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Impulse withstand and coordination per GB/T 14048.1, clearances and creepage per GB/T 16935.1, overvoltage category per GB/T 16895. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.