Dynamic braking versus regenerative braking on a VFD

Where does decelerating energy go? One burns it as heat, the other feeds the grid. This page covers wiring, efficiency and which to use.

1. How it works

When the motor decelerates or is driven by a load it becomes a generator, pumping energy back to the DC bus and raising its voltage. Unchecked, a 380 V drive bus exceeds 700 V and trips OV. Energy can either be burnt in a resistor via a brake unit, or inverted back to the grid via a regen unit. The first is cheap and simple, the second saves power but costs more and needs a clean grid.

2. Numbers and practice

Dynamic braking uses a brake unit and resistor; above a threshold like 680 V the unit conducts and dumps current into the resistor as heat. Resistors are 1~5 kW, 50~200 Ω, cost about 10%~20% of the drive, wire simply and suit any grid, but waste energy and need ventilation. Good for cranes and machines with occasional braking.

3. Pitfalls and fixes

Regenerative braking inverts the bus energy back to the grid at 85%~95% efficiency, paying off on continuous braking like big centrifuges and lowering hoists. But the unit costs 3~5× dynamic braking, needs a clean non-islanded grid and adds harmonic, needing a reactor. The trap is fitting regen for rare braking where payback is slow, or undersizing the resistor so it burns on continuous duty.

4. Dynamic vs regenerative braking

ItemDynamic brakingRegenerative
Energy pathResistor heatBack to grid
EfficiencyAll lost85%~95% recover
Cost10%~20% of drive3~5× dynamic
DutyOccasionalContinuous high
Grid needNoneClean, no island

5. Notes

Pick dynamic for occasional braking, calculate payback before regen for continuous duty. Size the resistor with margin for continuous braking. Regen is costly and grid-sensitive, add a reactor for harmonics.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; power quality per GB/T 14549. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Regen on rare braking pays back too slowly; use dynamic first
② Undersized brake resistor burns on continuous duty
③ Regen on islanded grid has nowhere to send power and trips OV

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.