How to compensate low-frequency torque loss on a VFD

When speed drops to a few Hz the load stalls, yet the motor is fine; torque boost is usually mis-set. This page explains the cause and three fixes.

1. How it works

At low frequency the output voltage is already low and stator resistive and leakage drops take a bigger share, so air-gap flux and torque collapse. At 50 Hz the drop is about 5% of voltage, but at 3 Hz it can exceed 30%, leaving only 50%~70% rated torque. The motor starts poorly and trips OL under load. Vector control avoids this by current decoupling; V/F drives must lift low-voltage gain manually.

2. Numbers and practice

Torque boost adds extra voltage at low frequency to recover lost flux. Auto boost self-adjusts; manual boost is set by load: 2%~5% light, 8%~12% heavy. Above 15% the core saturates, no-load current spikes and the motor overheats. Raise it gradually until rated load runs without OL and no-load current stays reasonable.

3. Pitfalls and fixes

Also raise start frequency from 0.5 to 2~3 Hz so flux builds before loading, and lengthen acceleration. Slip compensation or vector mode recovers speed under load automatically. The trap is over-boosting until the motor runs hot at no load, or under-boosting so it is still weak; tune with the real load, not by guess.

4. Low-frequency torque compensation

MethodWhen to useUpper limit
Torque boostV/F with constant torqueManual ≤12%
Higher start freqWeak start light load2~3 Hz
Longer accelBig inertia soft startWith boost
Slip comp/vectorDemanding jobsVector needs tuning
Voltage-drop compLong cable runsMeasure first

5. Notes

For weak V/F low speed, add torque boost from 2% until OL clears. Abnormally high no-load current means over-boost saturation. For demanding work use vector or slip compensation, steadier than crude boost.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.3; machines per IEC 60034-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Too much torque boost spikes no-load current and heats the motor
② Boost without longer accel still trips as flux is not built
③ Guessing boost by feel; tune with the actual load instead

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.