Apparent power and why transformers are rated in kVA

Transformers are rated in kVA rather than kW because the winding must carry magnetizing current as well as useful current. This page explains the power triangle and how power factor decides how much transformer you are actually buying.

1. How it works

Apparent power S equals the square root of P squared plus Q squared, in kVA. Active power P in kW does the work; reactive power Q in kvar builds and collapses magnetic fields. The winding copper carries both regardless of the split, so the rating is stated in kVA. The arithmetic is unforgiving: 100 kW at cos phi 0.7 demands 143 kVA, while the same 100 kW at 0.95 needs only 105 kVA. Poor power factor literally makes you buy a larger transformer for the same output.

2. Practice and pitfalls

Size the unit from Pc divided by the target cos phi. If the plant sits at 0.75, compensate first: a 180 kW load needs 240 kVA at 0.75, which pushes you to the 315 kVA frame, but at 0.95 it needs only 190 kVA and the 250 kVA frame suffices. The capacitors cost a fraction of the price difference and cut losses too. Insist on kVA in contracts and nameplates, leave margin above the calculated value for load swings and aging, and remember that old transformers deliver less than their nameplate as insulation dries out.

3. P, S and Q relationship quick table

Active P (kW)cosφApparent S (kVA)Reactive Q (kvar)
1000.70143102
1000.8511862
1000.9510533
1800.75240159
1800.9519059

4. Notes

Rate transformers on apparent power, never on active power alone. Compensation to 0.95 before selection often drops the purchase one frame size; keep margin on top of the calculation.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power transformers are covered by the GB 1094 series and GB 20052, reactive power compensation by GB/T 15576, with reference to IEC 60076. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Sizing the transformer in kW and forgetting reactive share: at low cos phi the windings overload and the unit trips
② Skipping compensation and buying for cos phi 0.75: one extra frame purchased, losses and demand charges both higher
③ Selecting exactly at the calculated value with zero margin: load swings and aging leave no headroom

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.