Contact resistance: terminal heating and voltage drop

Real contact area is a few percent of apparent area; oxidation films dominate - aluminium oxide is insulating.

1. How it works

50mΩ at 10A means 0.5V drop and 5W of heat at one point; thermal runaway ends in arcing.

2. Practice and pitfalls

Find hot joints with IR scans, measure with a 4-wire milliohmmeter, and verify crimp quality by pull-out force.

3. Contact resistance reference

JointHealthy rangeMethodWarning sign
Crimp 2.5mm²<0.5mΩ4-wire ohm>15K rise
Bolted busbarμΩ rangeMicroohm + torqueDiscoloration
Relay contacts<50mΩLow-ohm meter>100mV drop
Terminal block<2mΩ4-wire ohmDrift after mating
Al-Cu jointUse transitionThermal compareGalvanic spots
Soldered wirePer gaugeVisual + pullCold joints

4. Notes

Apply the points above to Contact resistance; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 14315, GB 50149 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Crimping aluminium into copper terminals directly
② Judging crimps by hand feel
③ IR scanning without logging load current

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.