Inductive loads eat reactive power; capacitors supply it locally, QC=P(tanφ1−tanφ2).
Switching: contactors (slow, inrush), thyristor TSC (fast), SVG (continuous). Inductors appear as shunt reactors and detuning filters.
Size for light load too - fixed caps overcompensate at night and raise voltage.
| Method | Response | Cost | Notes |
|---|---|---|---|
| Contactor switching | Seconds | Low | Inrush |
| TSC | Milliseconds | Medium | No inrush |
| SVG | Continuous | High | Phase-balanced |
| Fixed caps | — | Lowest | Stable base load |
| Tuned branches | — | Medium | Compensation+filtering |
| Shunt reactors | — | Medium | Absorb capacitive VArs |
Apply the points above to Reactive power compensation; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 15576, GB 50227, GB/T 14549, GB/T 12325 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.