Why a thermal relay cannot replace temperature protection

A seized bearing or blocked cooling drives winding temperature up while current barely moves, and the thermal relay, which senses current not heat, stays silent until the winding burns.

1. How it works

A thermal relay heats a bimetal with the line current, so it responds to current and only infers heating. When a motor overheats from blocked ventilation, high ambient or a dragging bearing (mechanical power little changed, current up slightly), the current rise is small and the relay trips late or not at all. A failing bearing may raise current only 10~20%, far below 1.2 times setting, so the relay sits quiet while the winding cooks; it is over-current protection, not temperature protection.

2. Practice and pitfalls

Typical blind spots: a stopped cooling fan removes forced cooling so temperature climbs 30~50K with almost no current change; frequent starts build intermittent heat the relay averages out; off-nominal voltage shifts iron and copper loss that current reflects slowly; and an incipient turn-to-turn short changes total current little while a hot spot forms first. These need temperature sensing, PTC (trip about 120~155℃) or PT100 in the winding and bearing, feeding the PLC or protector for trip and alarm. Keep the relay as overload backstop and add temperature protection for the blind spots, with trip values set below the insulation class (B 130℃, F 155℃).

3. Relay versus temperature protection

FaultRelayTemp protectAction
Bearing dragCurrent +10-20%Direct senseBearing sensor
Fan stopNo change, +30-50KDirect senseWinding PTC
Frequent startShort overloadCumulativeElectronic model
Voltage offSlow currentDirect tempPT100
Turn shortSmall changeHot spotEmbed sensor
VerdictOver-current onlyTemperatureDual protect

4. Notes

Rule: the thermal relay is over-current protection, not temperature protection, and it is blind to heat faults with steady current. Add PTC/PT100 and bearing sensors on important motors for dual protection, set trip values below the insulation class, and keep the relay as backstop.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor thermal protection per GB/T 12350 and IEC 60034 series, safety GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Relying on relay for bearing drag: current too low to trip, winding burns first
② No thermal protect on fan loss: tens of K rise unseen, insulation ages fast
③ Using relay as temperature protection: wrong mechanism, local overheat blind

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.