A seized bearing or blocked cooling drives winding temperature up while current barely moves, and the thermal relay, which senses current not heat, stays silent until the winding burns.
A thermal relay heats a bimetal with the line current, so it responds to current and only infers heating. When a motor overheats from blocked ventilation, high ambient or a dragging bearing (mechanical power little changed, current up slightly), the current rise is small and the relay trips late or not at all. A failing bearing may raise current only 10~20%, far below 1.2 times setting, so the relay sits quiet while the winding cooks; it is over-current protection, not temperature protection.
Typical blind spots: a stopped cooling fan removes forced cooling so temperature climbs 30~50K with almost no current change; frequent starts build intermittent heat the relay averages out; off-nominal voltage shifts iron and copper loss that current reflects slowly; and an incipient turn-to-turn short changes total current little while a hot spot forms first. These need temperature sensing, PTC (trip about 120~155℃) or PT100 in the winding and bearing, feeding the PLC or protector for trip and alarm. Keep the relay as overload backstop and add temperature protection for the blind spots, with trip values set below the insulation class (B 130℃, F 155℃).
| Fault | Relay | Temp protect | Action |
|---|---|---|---|
| Bearing drag | Current +10-20% | Direct sense | Bearing sensor |
| Fan stop | No change, +30-50K | Direct sense | Winding PTC |
| Frequent start | Short overload | Cumulative | Electronic model |
| Voltage off | Slow current | Direct temp | PT100 |
| Turn short | Small change | Hot spot | Embed sensor |
| Verdict | Over-current only | Temperature | Dual protect |
Rule: the thermal relay is over-current protection, not temperature protection, and it is blind to heat faults with steady current. Add PTC/PT100 and bearing sensors on important motors for dual protection, set trip values below the insulation class, and keep the relay as backstop.