At the same point, three-phase and single-phase faults give very different currents. This page covers the calculation and difference to guide selection and setting.
A three-phase fault k3 shorts all three lines with no ground; it is symmetric and the current I k3 is about U n over Z k, the largest fault current and the basis for breaking capacity and busbar rating. A single-phase fault k1 is one line to ground or neutral, asymmetric, governed by positive, negative and zero sequence impedance together, so it is generally smaller.
In most networks three-phase current is the maximum; single-phase is roughly one over root three to one times that, depending on zero-sequence loop impedance. With good grounding and low loop impedance single-phase approaches three-phase; with long cable or poor ground it is much smaller and may fail to operate the protection. Select the breaker by I k3 but verify end single-phase I k1 exceeds the setting by 1.3 to 1.5 times or the ground fault will not trip.
| Type | Trait | Relative |
|---|---|---|
| 3-ph k3 | symmetric | largest |
| 1-ph k1 | asymmetric | smaller |
| Ratio | Ik1~Ik3/root3 | loop dep |
| Select | by Ik3 | breaking |
| Verify | calc Ik1 | must trip |
| End | Ik1 low | no trip risk |
Do short-circuit checks with both hands: breaking capacity by the largest three-phase, sensitivity by the smallest single-phase. At long-cable ends and poor-ground loops the single-phase current may be too low to trip, so compute it and add RCD or larger wire. Never trust the three-phase number alone.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage distribution follows GB/T 50054 and short-circuit GB/T 15544. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.