The small switch in the panel is an MCB, also used in control cabinets. This page opens it up to show how it trips and quenches the arc within milliseconds on short circuit.
A miniature circuit breaker (MCB) consists of housing, handle, moving/fixed contacts, arc chute, bimetal (thermal trip) and solenoid (magnetic trip). The handle up closes contacts locked by a latch; down opens. It integrates two protections: the bimetal bends from Joule heat to trip on overload with delay, and the coil magnetically pulls the armature instantly on short circuit. All in an 18 mm wide plastic case.
On overload above rated, the bimetal bends over seconds to tens of seconds and releases the latch, inverse-time (larger current trips faster). On short circuit at 5~10× rated, the coil field instantly (≤10 ms) pulls the armature to strike the latch and open. At opening an arc draws between contacts; the arc chute splits it into short arcs across metal plates, cooling and extinguishing, limiting energy.
The chute splits the long arc into series short arcs; each cathode drop ~20 V, total arc voltage above supply extinguishes it. Breaking capacity (6 kA, 10 kA) is the maximum short current it can safely clear; exceeding it bursts the case. Traps: a low breaking-capacity MCB on a high short-circuit bus explodes on fault; re-closing burnt contacts without replacement fails to clear; assuming an MCB stops leakage, it does not sense earth leakage (see RCD).
| Part | Role | Protection |
|---|---|---|
| Bimetal | Bends on heat | Overload |
| Solenoid | Instant pull | Short |
| Arc chute | Splits arc | Quench |
| Mechanism | Latch close | Manual |
| Case | 18 mm | Insulate |
An MCB uses a bimetal (thermal inverse-time overload) and a solenoid (magnetic ≤10 ms short), with an arc chute splitting the arc to quench. Breaking capacity (6/10 kA) is the max safe fault current. It does not sense leakage; that needs an RCD.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; MCB per IEC 60898. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.