P, Q and S form a right triangle, and cos phi is adjacent over hypotenuse. This page draws the triangle and gives the steps to compute cos phi and Q on site.
The power triangle has apparent S as hypotenuse, active P along the base and reactive Q as the vertical, with S squared equals P squared plus Q squared, tan phi equals Q over P and cos phi equals P over S, the angle between voltage and current. Inductive Q is positive, capacitive negative, and the geometry makes the three powers obvious at a glance.
From readings, cos phi equals P over S; if you know P and Q first find S as root of P squared plus Q squared then cos phi, or cos phi equals one over root of one plus Q over P squared. With current, voltage and P, S is root three U I for three-phase and cos phi is P over S. Example: P 80 kW, Q 40 kvar gives S about 89.4 kVA and cos phi about 0.894.
| Known | Find | Formula |
|---|---|---|
| P,S | cos | P/S |
| P,Q | S | root(P2+Q2) |
| P,Q | cos | P/root(P2+Q2) |
| Example | P80 Q40 | cos 0.894 |
| 3-phase | S | root3 U I |
| Target | cos 0.95 | tan 0.329 |
The power triangle is the electrician pocket calculator: grab P Q S from the meter and cos phi is instant. Low factor means add capacitors, not a bigger transformer. Size correction by Qc equals P of tan phi1 minus tan phi2, target about 0.95 for economy.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 12325 and correction GB/T 15576. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.