The power triangle and power-factor calculation

P, Q and S form a right triangle, and cos phi is adjacent over hypotenuse. This page draws the triangle and gives the steps to compute cos phi and Q on site.

1. How it works

The power triangle has apparent S as hypotenuse, active P along the base and reactive Q as the vertical, with S squared equals P squared plus Q squared, tan phi equals Q over P and cos phi equals P over S, the angle between voltage and current. Inductive Q is positive, capacitive negative, and the geometry makes the three powers obvious at a glance.

2. Practice and pitfalls

From readings, cos phi equals P over S; if you know P and Q first find S as root of P squared plus Q squared then cos phi, or cos phi equals one over root of one plus Q over P squared. With current, voltage and P, S is root three U I for three-phase and cos phi is P over S. Example: P 80 kW, Q 40 kvar gives S about 89.4 kVA and cos phi about 0.894.

3. Triangle calculation

KnownFindFormula
P,ScosP/S
P,QSroot(P2+Q2)
P,QcosP/root(P2+Q2)
ExampleP80 Q40cos 0.894
3-phaseSroot3 U I
Targetcos 0.95tan 0.329

4. Notes

The power triangle is the electrician pocket calculator: grab P Q S from the meter and cos phi is instant. Low factor means add capacitors, not a bigger transformer. Size correction by Qc equals P of tan phi1 minus tan phi2, target about 0.95 for economy.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 12325 and correction GB/T 15576. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Using S as P gives cos phi of one, absurd
② Forgetting root three on three-phase scales S and cos phi wrong
③ Targeting unity like 1.0 over-corrects and over-voltss

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.