Contactor main and auxiliary contact numbering rules

On a contactor, 1/3/5 and 2/4/6 are main contacts, 13/14 and 21/22 are auxiliary. Misread the numbers and wiring goes wrong.

1. How it works

Three-phase main contacts are fixed as L1/T1, L2/T2, L3/T3 (old 1/2, 3/4, 5/6). For each pair the odd number is the line side, even is the load side: 1 in 2 out, 3 in 4 out, 5 in 6 out. They carry motor current, so torque them hard. Numbering follows IEC 60445 / GB/T 4026 so drawing and device match: line to supply, load to motor.

2. Numbers and practice

Auxiliary contacts serve control, small current. Standard: 13-14 is one NO (normally open), 21-22 one NC (normally closed); a second NO is 33-34, NC 41-42. NO is open before pull-in and closed after; NC is the reverse. Self-hold uses NO 13-14, interlock uses the other contactor NC 21-22. The contact chart or a buzzer meter reading is the safe check.

3. Pitfalls and fixes

Pit one: wiring the motor to an auxiliary contact, the current welds it. Pit two: treating 13/14 as NC, the self-hold is reversed and the motor only jogs. Pit three: loose auxiliary screws give an intermittent control circuit and random stops. Cross-check the nameplate contact map with a meter, torque mains hard, lightly but surely the auxiliaries, then re-check.

4. Contactor contact numbering quick table

ItemNumberNature
Main 11 in / 2 outL1 main
Main 23 in / 4 outL2 main
Main 35 in / 6 outL3 main
Aux NO13-14NO, closes on pull
Aux NC21-22NC, opens on pull
Second33-34/41-42Expansion

5. Notes

Rule: main contacts odd-in even-out (1-2/3-4/5-6), high current torque hard; aux 13-14 NO, 21-22 NC, self-hold uses NO, interlock uses NC. Match the nameplate with a meter, never by memory.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contact numbering per GB/T 4026 (IEC 60445), contactor product per GB/T 14048.4. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Wiring motor to an auxiliary contact: current welds it
② Treating 13/14 as NC: self-hold reversed, motor only jogs
③ Loose auxiliary screws: intermittent control, random stops

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.