To size couplings and brakes you need motor rated torque; this page computes it from power and speed in one move.
Rated torque Tn (N·m) = 9550 × Pn(kW) / n(r/min), the 9550 from 60×1000/(2π). Example 15 kW at 1460 r/min: Tn=9550×15/1460≈98.1 N·m. Using synchronous speed instead gives a slightly low value because real n is lower and torque higher; always prefer the plate actual speed. The formula applies to AC and DC shaft output.
You need torque to size couplings, brake torque and gearboxes. Brake torque must be ≥1.5×Tn to prevent slip on cranes; gearbox rated output must exceed load-referred torque with a service factor. Guessing Tn leads to weak brakes (slip) or small gearboxes (broken shaft). Trap: computing Tn from sync speed under-sizes the brake marginally.
Steps: take Pn and n → Tn=9550·Pn/n → add margin (brake 1.5×, gearbox service factor 1.5~2). If only power and no speed, estimate ns by poles then subtract 2%~5% slip. Check: at constant speed load current ratio ≈ torque ratio, so full current near Tn. Rule: power over speed times 9550; braking and gearing depend on it. Under VFD overspeed n drops and Tn drops proportionally in the constant-power region.
| Power | Speed | Tn N·m |
|---|---|---|
| 7.5 kW | 1450 | 49.3 |
| 15 kW | 1460 | 98.1 |
| 22 kW | 1470 | 142.9 |
| 37 kW | 1480 | 238.6 |
| 45 kW | 1480 | 290.4 |
Tn=9550×Pn/n using actual plate speed, not sync (which under-sizes). Brakes need ≥1.5×Tn, gearboxes add service factor 1.5~2. Under VFD overspeed Tn drops. Current ratio ≈ torque ratio for a check.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machines per IEC 60034-1; machinery per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.