An AC breaker moved to a DC circuit often fails to interrupt the arc and can burst. DC has no current zero-crossing, so the arc is far harder to extinguish.
AC current crosses zero 100 times per second, so the arc self-extinguishes at each zero. DC has no zero, so the breaker must stretch, cool and magnetically blow out the arc. The same breaker therefore interrupts far less DC: a 10A miniature breaker rated 6kA AC might manage only 1.5kA at DC250V and less at DC500V. The nameplate lists separate AC and DC ratings, and the single-pole DC voltage ceiling is only about 60~125V, read the maker curve.
De-rate the rated current in DC: run continuous load at 60%~80% of rating because DC heat concentrates. Raise the voltage by series-connecting poles, two poles reach DC250V, four poles DC500V. Contact and relay coils also need a DC category. For inductive loads such as motors pick a higher breaking capacity and allow for the reverse electromotive force on opening.
Never put an AC miniature breaker on DC. At low DC voltage it seems fine until a short strikes and the arc will not clear, welding the contacts and melting the case. Do not use a single pole above its DC ceiling. Battery racks, PV strings and vehicle supplies are DC and need DC-curve breakers with correct polarity.
| Item | AC circuit | DC circuit |
|---|---|---|
| Zero crossing | Yes, 100/s | None, hard to clear |
| Breaking capacity | e.g. 6kA labelled | 1/3~1/4 of AC |
| Rated current | Full load ok | De-rate to 60%~80% |
| Pole use | By phase count | Series poles raise voltage |
| Use case | Mains, motors | Battery, PV, AGV |
| Misuse result | — | Arc weld, melt, burst |
Rule: DC has no zero, the arc needs brute force. Pick a DC-curve or dedicated DC switch, de-rate current and series poles for voltage, watch polarity. Battery, PV and vehicle supplies must follow the DC category, never substitute an AC miniature breaker.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: DC application of low-voltage switchgear per GB/T 14048.1 and GB/T 14048.2, with breaking tests referenced to IEC 60947. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.