Variable frequency drive speed control of induction motors and its characteristics

A variable frequency drive speeds an induction motor while keeping torque, by holding the voltage to frequency ratio. This page explains V/f control, the two regions around the base frequency and the field tuning of voltage and frequency.

1. How it works

The motor flux is roughly proportional to U over f, so to keep flux constant the voltage must fall in proportion to frequency: that is constant V/f or V per Hz control. Below base frequency, say 50 Hz, it is the constant torque region where U and f drop together and torque stays near rated; above base frequency it is constant power, voltage capped while frequency keeps rising so torque falls inversely. The drive rectifies then inverts to adjustable frequency and voltage PWM. At low frequency the stator resistance drop looms larger, so a small torque boost voltage is added to avoid weak torque.

2. Practice and pitfalls

Below base frequency at 380 V and 50 Hz, dropping to 10 Hz about 76 V holds flux and torque for conveyors and lifts. Above base, at 100 Hz the voltage stays 380 V, power constant and torque halved for high speed light spindles. Open loop V/f start torque is about 1.5 times rated, less than star delta but smooth; vector control reaches over 2 times with stable low speed torque. In commissioning, enter the nameplate data first, pick the V/f curve, add boost for heavy load or long cable and cut it for light load to avoid over flux heating. Below 20 Hz the self cooling fan slows, so force cooling or derate, set carrier 2 to 8 kHz as a compromise, and ground the shielded cable away from analog lines.

3. Two regions of VFD speed control

Frequency bandVoltageTorqueUse
below baseU falls with fconstant torqueconveyors lifts
base 50 Hz380 V ratedrated torquerated point
above basecapped 380 Vconstant power half torquehigh speed spindles
low below 20 Hzneeds boostavoid weak torqueforce cool derate
tuningenter nameplatepick V/f curveboost at low freq

4. Notes

VFD control centres on constant V/f to hold flux: constant torque below base, constant power above. Commission with nameplate data and the right curve, boost at low frequency, force cool or derate when slow, and keep carrier and shielding sane. Vector control buys larger low speed torque when needed.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable speed drives per GB/T 12668 (IEC 61800); motor rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① skip torque boost at low frequency: resistance drop starves flux and torque
② run long at low frequency without cooling: slow fan overheats the winding
③ enter wrong motor data: V/f curve distorts and current heats

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.