Efficiency versus power factor on the nameplate

Both are on the plate, but one governs wasted power and the other line loss; do not treat them alike. This page separates the two and their effect on bill and cable.

1. How it works

Efficiency η = mechanical output / electrical input, reflecting the motor own losses (copper, iron, friction); higher means less wasted electricity. Power factor cosφ = active / apparent power, reflecting how much of the current does work versus reactive magnetising current; lower means more reactive current, hotter lines and less transformer headroom. Different: low η directly raises the bill, low cosφ heats lines and limits load.

2. Numbers and practice

Both peak at 70%~100% load; below 40% cosφ collapses (from 0.85 to 0.3) and η also drops. So oversized or undersized motors are inefficient. Pick power so the running point sits at 75%~90% load. Traps: a huge motor on a tiny load has low cosφ and reactive penalty from the utility; a too-small motor overloaded has low η and overheats.

3. Pitfalls and fixes

To save bill, choose high-efficiency motors (IE3/IE4, 2%~8% above IE1) run in their efficient zone. To cut line loss, add capacitor compensation on big or light-load motors to lift cosφ above 0.9, shrinking current and I² loss. Current I = P/(√3·U·cosφ); raising cosφ from 0.7 to 0.95 cuts current about 26%, allowing a smaller wire. Plate η and cosφ are at rated point and float with load.

4. Efficiency vs power factor

MetricMeaningEffect
ηOutput/inputHigher saves
cosφActive/apparentLow loss
Best load70%~100%Peak both
Light<40%cosφ dropsReactive penalty
CompensateCapacitor upCurrent down

5. Notes

Efficiency governs self waste, power factor governs line loss and reactive. Best load 70%~100%; light load collapses cosφ. Use IE3/IE4 in efficient zone; compensate light loads to cosφ>0.9, cutting current ~26%. Plate values are at rated point.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor efficiency per GB/T 18613; power factor per GB/T 14549. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Huge motor on tiny load draws reactive penalty
② Too-small motor overloaded has low η and overheats
③ No compensation on light load wastes line capacity

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.