The grid often mixes 50 Hz with harmonics and noise, no longer a pure sine. This page shows how different-frequency sines add into a complex wave and why mains measurement must account for harmonic content.
In a linear circuit several sines of different frequency simply add point by point, so the base 50 Hz plus 3rd at 150 Hz and 5th at 250 Hz yields a distorted non-sinusoid. That is the Fourier idea: any periodic wave splits into fundamental plus harmonics. Because phasors apply only to equal frequencies, you add these by instantaneous values, not by phasor.
The RMS of the sum is the root of the sum of squares of each component RMS, and the peak is no longer root two times RMS, it can be higher and spiky. Average and form factor change too, so a cheap average-responding meter lies and only a true RMS meter reads the real heating value. A VFD output is a kilohertz PWM carrier on top of 50 Hz base.
| Component | Freq | Effect |
|---|---|---|
| Fundamental | 50 Hz | main energy |
| 3rd | 150 Hz | neutral |
| 5th | 250 Hz | heating |
| 7th | 350 Hz | torque ripple |
| Sum RMS | root squares | true RMS |
| Measure | FFT | spectrum |
When a wave is not sine, think superposition. Use a true RMS meter and an FFT scope to see components. Harmonics raise heating, vibration and noise on mains gear, so do not watch only the fundamental; treat harmonics at source with reactors and at end with filters.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Power quality follows GB/T 14549 and measurement IEC 61000. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.