The insulation class decides how high a temperature the winding can survive; wrong choice or over temperature ages insulation and halves life. This page explains class A E B F H limits and how to measure temperature rise.
Common classes: A 105 C E 120 B 130 F 155 H 180. The number is the maximum allowable winding temperature. Exceeding it accelerates insulation ageing sharply; rule of thumb every 10 C above limit halves the remaining life. Choose class by ambient and cooling.
Temperature rise equals winding temperature minus ambient with 40 C as base. Measure by resistance method most accurate or by embedded sensor or surface thermocouple approximate. Pit one: at 50 C cabinet in summer still using 40 C base means the winding already exceeds class; pit two: running an F class motor as B class over temp burns it; pit three ignoring hot spot at core end.
| Class | Limit temp | Base ambient | Allowed rise |
|---|---|---|---|
| A | 105 C | 40 C | 65 K |
| E | 120 C | 40 C | 80 K |
| B | 130 C | 40 C | 90 K |
| F | 155 C | 40 C | 115 K |
| H | 180 C | 40 C | 140 K |
| Base | use 40 C | hot day +10 | recompute |
Classes are A105 E120 B130 F155 H180 with rise measured from 40 C base; resistance method is most accurate. Recompute when ambient is high and never run an F class motor as if B class. Over temp burns insulation and halves life per 10 C.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machine insulation see IEC 60034-1 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.