Voltage-current relations in pure R, L and C AC circuits

Resistor, inductor and capacitor behave completely differently under AC: in phase, lagging and leading. This page sets out the voltage-current relations and the reactance formulas, the foundation of all AC work.

1. How it works

A pure resistor keeps voltage and current in phase, so power is always positive and P equals U I. A pure inductor makes current lag voltage by 90 degrees, storing and returning energy with zero average power. A pure capacitor makes current lead by 90 degrees, also a storage element with zero average power. Rule: inductor voltage leads current, capacitor current leads voltage.

2. Practice and pitfalls

Inductive reactance XL equals omega L and grows with frequency; at 50 Hz a 0.1 henry coil is about 31.4 ohm. Capacitive reactance XC equals one over omega C and shrinks with frequency; at 50 Hz a 10 microfarad cap is about 318 ohm. These two numbers set the impedance and are the basis for filters and correction.

3. Single-element AC traits

PartPhaseImpedance
Resistorin phaseR
Inductorlag 90XL=wL
Capacitorlead 90XC=1/wC
50Hz 0.1HinductiveXL 31.4
50Hz 10uFcapacitiveXC 318
LossR onlyL/C zero

4. Notes

First decide whether a load is resistive, inductive or capacitive when troubleshooting AC. Motors and transformers are inductive; correction caps and cable capacitance are capacitive. The phasor relation tells you at once whether low power factor is too much inductance or over-correction.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Circuit basics follow GB/T 2900 and power quality GB/T 14549. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Measuring L or C on a resistance range gives meaningless numbers
② Treating an inductor as a resistor misstates the heating by far
③ Ignoring the 90 degree phase reverses the correction direction

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.