How the six terminals in a motor box are wired to star or delta. This page covers U1/U2 identification, the two connections and field rewiring notes.
A three-phase stator has three windings, each with start and end, six terminals marked U1 U2, V1 V2, W1 W2 where U1 V1 W1 are starts and U2 V2 W2 ends; the nameplate gives the voltage for each connection, such as 380 V delta or 660 V star. Wrong connection means wrong voltage on the winding.
In star the three ends U2 V2 W2 are tied to a neutral and the starts go to the supply, so each winding sees phase voltage, 220 V on a 380 V system. In delta U1 joins W2, V1 joins U2, W1 joins V2, the windings close into a ring and each sees line voltage, 380 V. A given motor uses delta at 380 V and star at the higher voltage; miswire and the winding is over or under volted.
| Conn | Wiring | Per-winding V |
|---|---|---|
| Terminals | U1V1W1 start | U2V2W2 end |
| Star Y | tie U2V2W2 | 220 V |
| Delta D | U1-W2 ring | 380 V |
| Nameplate | 380 V = D | 660 V = Y |
| Wrong Y | low torque hot | under |
| Wrong D | insul break | over |
Read the nameplate voltage and connection before wiring, follow terminal numbers not wire colour. Star-delta started motors run in delta and start in star, so the contactor logic must match. After rewiring, jog to confirm direction and current, then load; loose terminals are a common fault, tighten on schedule.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machines follow GB/T 755 and marking GB/T 1971. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.