Paralleling multiple power supplies: conditions and current sharing

Paralleling requires equal voltage, same polarity, matched output characteristics and a sharing scheme.

1. How it works

Mismatched set-points drive circulating current: 0.2V over 0.1Ω is 2A of internal fight.

2. Practice and pitfalls

Options: droop (no interconnect), master-slave, share bus, or isolation diodes / ideal-diode ORing for redundancy.

3. Sharing method comparison

MethodPrincipleProsLimit
DirectNatural resistanceSimpleCirculating current
DroopArtificial rNo wiresWorse regulation
Master-slaveMaster setsAccurateSingle point
Share busCommon signalAccurate+redundantWiring
Series diodesBlock backfeedNo circulationDrop loss
Ideal diodeMOS ORingTiny lossCost

4. Notes

Apply the points above to Paralleling multiple power supplies; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 19826 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Paralleling supplies to gain current without sharing
② Casually rating ORing diodes
③ No redundancy for the master in master-slave systems

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.